SCU battery management and hybrid inverter systems
SCU Battery Container
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|---|
| Battery container | ✅ | ❌ | ✅ | |
Configuration
SCU Battery Container
In the SCU interface:
- Go to "Maintenance"
- Go to "Comm Settings"
- Go to "PCS"
- Under "BMS: Number of devices" -> Set this to the amount of batteries / BMS systems that are connected.
GRES-300-200
GRES uses the same SCU interface path, but configure based on battery rooms (up to 4 groups):
- Go to "Maintenance" → "Comm Settings" → "PCS"
- Set "BMS: Number of devices" to your battery room count (1-4 for GRES-300-200)
- Ensure PCS remote control is enabled for curtailment
- Modbus address: Default
1(matches driverDEFAULT_BUS_ADDRESS: 1)