AppareilsEnergy meterSolis
Compteurs d'énergie Solis raccordés au réseau
Appareils pris en charge
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Solis Grid-Tie Meter (via Inverter/EPM) | ✅ | ✅ |
| Autarco Grid-Tie Meter (via Inverter/EPM) |
Connexion
Ethernet
Pour un câblage Ethernet correct : Suivez les directives pour le câblage Ethernet.
RS485
Connectez les fils RS485 au port de communication de l'appareil Solis (Inverter ou Export Power Manager).
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| GND (optionnel) | RS GND | GND | Not available | G |
Configuration
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Assurez-vous que l'appareil est configuré avec les paramètres Modbus suivants pour correspondre aux spécifications du pilote :
- Baudrate : 9600
- Bits de données : 8
- Bits d'arrêt : 1
- Parité : Aucune
- Adresse Modbus : 1 (par défaut) - Plage : 1 à 254