SmartgridOne logo
SmartgridOne logo
Démarrage rapideInstallationRéseauDirectives de câblage et de connectivitéApp
AperçuNouvelles intégrations
ABBAccuenergyAcrelAlgodueAnexoBMRChargeeChintDonnées du compteur nuageuxDornscheidtFluviusFroniusHagerHomeWizardHuaweiIneproIskraJoulzKaifaKamstrupLandis+GyrLegrandM-BusMetcomP1ApiPhoenix-ContactPiloteSagemcomCompteur d'énergie auto-configuréSeneca S604SessyCompteurs d'énergie ShellySiemensSmappeePrêt pour le réseau intelligentSocomecSolaxSunwodaTillquistVictronWeidmüllerYouLessZiv
SpécificationsLEDs de statutTemps de réponse de contrôleTutoriels vidéoCertificatsLicenceSécurité, maintenance et avis légaux
AppareilsEnergy meter

Huawei Energy Meters

Huawei

Supported Devices

Device TypeModbus TCP (Ethernet)
Energy Meter via Smartlogger✅
Image 1

The Huawei SmartLogger can be used to read and control energy meters/solar inverters/batteries.

Wiring - Ethernet

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

Configuration

1. Activating Modbus in the SmartLogger

  1. Surf to the IP address of the SmartLogger.
  2. Login to the SmartLogger (default password: "Changeme").
  3. Change “Link setting” to “Enable (Unlimited)”.
  4. Set “Address mode” to “Communication address”.
  5. Choose the Modbus address of the logger. We recommend that this is different from the addresses of the inverters (see also the next step in the manual).
  6. Click submit.
Image 1
Image 1

2. Device Modbus Addresses

The smartlogger can connect both inverters and energy meters via 3 COM ports. Adding and giving Modbus addresses can be done automatically or not.

However... all Modbus addresses must be different!

Image 1

To adjust this, it is best to first adjust the possible addresses per COM port so that there is no overlap.

Image 1

Then you remove the devices with the same address and add them back with an address different from all other devices.

Image 1

HomeWizard

HomeWizard Compteurs d'Énergie

Inepro

Compteurs d'énergie Inepro

On this page

Supported DevicesWiring - EthernetConfiguration1. Activating Modbus in the SmartLogger2. Device Modbus Addresses