Compteurs d'énergie Pilot
Appareils pris en charge
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Pilot SPM33 | ✅ | ✅ |
Câblage
RS485
Les bornes RS485 se trouvent à l'arrière de l'appareil.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| 13 (A+) | RS485 A | RS485_POS | RS485 A | TX+ |
| 12 (B-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 14 (Shield) | RS GND | GND | Not available | G |
Note
Note
Alimentation électrique Assurez-vous que l'appareil est alimenté à l'aide des bornes 1 (L/+) et 3 (N/-). La plage d'alimentation auxiliaire est de 85 à 265 V CA ou de 100 à 300 V CC.
Configuration
Avertissement
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Utilisez les paramètres Modbus suivants dans l'assistant de configuration de l'appareil du Controller. Il s'agit des paramètres par défaut du compteur :
- Débit en bauds : 9600
- Adresse Modbus : 1 (ou l'adresse configurée sur le compteur)
- Parité : Aucune
- Bits d'arrêt : 1
- Bits de données : 8