SmartgridOne logo
SmartgridOne logo
AppCertifikaterController
Eksterne Signaler
Enheder
Elbilopladningsstation
Energimåler
Gasmåler
Kedel
Nye integrationer
Plc
Pv Hybrid- og batteri-invertere
a-TroniXABB, FIMERADS-TecAlphaESSAmpowrAngileAnklous PV, Hybrid og Batteri InvertereAPsystemsAteps Batteri
Autarco
BeauventC-BatteriCellpowerChisageDanfossDeltaDET Power PV, Hybrid og Batteri InvertereDEYEDiehl-AkoDMEGC InvertereDynessDysun EnergyEcosourcenEenovanceElecnovaEnbrilionEnergreenEnerlutionEnjoyPowersEnphaseEP UdstyrESY InvertereEVEFortonaForud for
Foxess
FoxESS GMAXFoxESS H-serieFoxESS R-Serie
FraxFroniusGoodWeGotionGrønnere / Alfen
Growatt
HiteHithium
Huawei
Hypontech
Hyxipower
iWellJinkoKacoKehuaKostal
Kstar
MarstekMastervoltMidTeQMotomaOctave EnergyOmniPowerPixiiPower-SonicPoweroadPylontechRegitecRenonRenoveringRitarSAJSchneider SunEzySchucoSCUSE2200H til SE6000HSessySigenergySinexcel
Sma
Socomec
Sofar
Solaredge
SolarlogSolarMaxSolarwattSolaxSolinteg
Solis
Solplanet
Sungrow
SunwaytechSunwoda
Sunwoda
Sus-PowerTeclomanTeploreTesvoltVaconVictronVolstoraWattsNextWeihengXantrexZendure SolarFlowZetaraZeversolar
Sky
Vandmåler
Varmepumpe
Vekslende Belastninger
Fejlfinding
InstallationKom godt i gang
Konfiguration fra A til Z
Kontrolresponstid
Kundespecifik
LicensNetværkRetningslinjer for ledningsføring og tilslutningSikkerhed, vedligeholdelse og juridiske meddelelserSpecifikationerStatus-LED'er
Tilbehør
Værktøjskasse
Videovejledninger
EnhederPv Hybrid- og batteri-invertereFoxess
logo

Understøttede enheder

Device TypeModbus TCP (Ethernet)RS485CurtailmentMinimum device firmware version
H3 (Non-Pro, Non-Smart): → ❗Se note nedenfor ❗❌✅❗(se nedenfor)Master: 2.05, Manager: 1.85 (*)
H3 AIO (All-In-One)✅❌Master: 1.33, Manager: 1.37 (*)
H3-Smart

FoxESS GMAX

Previous Page

FoxESS R-Serie

Next Page

On this page

Understøttede enhederH3 (Non-Pro, Non-Smart)Understøttede firmwareversionerKabelføringEthernetRS485RS485 H3 ProKonfiguration for H3 (Non-Pro, Non-Smart) og H1-G21. Aktivering af overvågning og styring af inverter2. Aktivering af fjernstyring3. Deaktivering af måler4. Indstilling af inverteradresseHurtigere scanningFlere invertereKonfiguration for H3-smart og H3-Pro
⌛ (under udvikling)
Master: 1.25, Manager: 1.14 (*)
H3-ProMaster: 1.62, Manager: 1.34 (*)
H1(eksperimentel, kræver test)Master: 1.70, Manager: 1.78 (*)
H1-G2⌛ (under udvikling)Master: 1.40, Manager: 1.54 (*)
P3-SH✅ (eksperimentel)✅ (eksperimentel)Master: 1.62, Manager: 1.34 (*)
Forsigtighed
Forsigtighed

H3 (Non-Pro, Non-Smart)

H3 (Non-Pro, Non-Smart) har forskelligt kommunikationsprotokol afhængigt af inverterens 'master version' og 'manager version'. Vælg den tilsvarende integration baseret på inverterens softwareversioner.

✅ Begrænsning understøttes for firmware versioner master v.2.05 og manager v.1.85 og derunder.

⌛ Begrænsning er under udvikling for firmware versioner master v.2.06 og manager v.1.86 og derover.

Advarsel
Advarsel

H3 (non-pro, non-smart) serien bruger en forskellig kommunikationsprotokol end H3 Pro og H3 Smart serien. Derfor skal du, når du vælger enhedstype i SmartgridOne Controller, være meget sikker på, at du vælger den korrekte type.

Note
Note

Understøttede firmwareversioner

(*) Integration kan fungere med ældre firmwareversioner, men disse er ikke testet.

Image 1

Kabelføring

Advarsel
Advarsel

Standard modbus adresse eller enheds-ID er 247. Husk dette, når du scanner efter en inverter. Du kan ændre minimum og maksimum bus adresser, som controlleren vil scanne i scanneparametrene.

Ethernet

For korrekt ethernet kabelføring: Følg retningslinjerne for ethernet kabelføring.

Advarsel
Advarsel

Du kan ikke forbinde den via WiFi dongle.

RS485

Inverteren kan forbindes til SmartgridOne Controller via RS485. Dette sker gennem forbindelse [J] på billedet nedenfor.

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
Logger 485A / pin 1RS485 ARS485_POSRS485 ATX+
Logger 485B / pin 2RS485 BRS485_NEGRS485 BTX-
N/ARS GNDGNDNot availableG
Image 1

RS485 H3 Pro

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
EMS 485A / pin 17RS485 ARS485_POSRS485 ATX+
EMS 485B / pin 18RS485 BRS485_NEGRS485 BTX-
N/ARS GNDGNDNot availableG
Image 1

Konfiguration for H3 (Non-Pro, Non-Smart) og H1-G2

1. Aktivering af overvågning og styring af inverter

Styringen skal aktiveres via inverteren, og måleren skal deaktiveres. Dette gøres via displayet i menuen Feature Parm. Åbn først menuen Feature Parm som følger:

  1. Gå til Menu.
Image 1
  1. Indtast adgangskode. Standard er 0000.
Image 1
  1. Vælg Indstillinger.
Image 1
  1. Vælg Feature Parm.

2. Aktivering af fjernstyring

Brug displayet videre fra Feature-siden til at aktivere styringen, følg nedenstående trin:

  1. Vælg Fjernstyring.
Image 1
  1. Sæt den til Aktiver.
Image 1

3. Deaktivering af måler

Måleren skal deaktiveres. Styringen overtages af SmartgridOne Controller. Derfor skal måleren ikke være tilsluttet inverteren, men til SmartgridOne Controller. For at deaktivere måleren i indstillingerne, følg disse trin:

  1. Gå tilbage til Feature-siden.
  2. Vælg Meter1.
Image 1
  1. Vælg Sæt.
Image 1
  1. Sæt den til Deaktiver.
Image 1

4. Indstilling af inverteradresse

Inverterens adresse kan også indstilles via displayet.

  1. Gå til Indstillinger-menuen som beskrevet tidligere.
  2. Vælg Kommunikation.
  3. Vælg RS485.
  4. Vælg Enheds-ID.
  5. Indstil enheds-ID til ønsket adresse. Hvis du forbinder flere enheder til samme RS485 bus, skal hver have en unik adresse.
Image 1
Tip
Tip

Hurtigere scanning

SmartgridOne Controller starter scanningen ved adresse 1 som standard. Hvis du vælger en lavere adresse, vil din inverter blive fundet hurtigere.

Advarsel
Advarsel

Flere invertere

Hvis du har flere invertere, er det vigtigt at sætte parallelle adresser, så hver inverter har en forskellig adresse.

Konfiguration for H3-smart og H3-Pro

Fjernstyring er aktiveret som standard, du behøver ikke ændre indstillinger.

Ændring af inverteradresse (eller enheds-ID) kan gøres på samme måde som for H3 (se ovenfor).