Ampowr Invertere
Ampowr Invertere
Understøttede Enheder
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 |
|---|---|---|---|
| Ampihome | Enkeltfase | ❌ | ✅ |
| Trefase | |||
| Hybrid | ✅ |
Kabelføring
SmartgridOne Controller og Ampihome inverterne kommunikerer via RS485 eller Ethernet.
Ethernet
For korrekt ethernet-kabelføring: Følg retningslinjerne for ethernet-kabelføring.
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Pin 7 (White-Brown) | RS485 A | RS485_POS | RS485 A | TX+ |
| Pin 8 (Brown) | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |

Advarsel
Advarsel
Jeg kan ikke finde min Ampihome inverter For Ampowr hybrid invertere er standard busadresser 247 for Modbus RTU og 255 for Modbus TCP. SmartgridOne Controller scanner efter enheder på alle adresser fra 1 til 255. Derfor kan scanningen tage noget tid.
TIP: Hvis du kender busadressen på din inverter, kan du sætte den i SmartgridOne Controller for at fremskynde scanningen.
Konfiguration
Ampihome Enkeltfase
Ampihome Enkeltfase skal sættes til Slave Secondary Port:
- Åbn ESS Link appen
- Vælg "My" nederst til højre
- Vælg "My Device"
- Vælg "Comm No." på enheden
- Vælg "Parameter Settings"
- Sæt "Working Mode" til "Timed Charge Mode (C&D)"
- Vælg "Advanced" øverst til højre
- Sæt "BMS1 RS485 Multiplexing" til "Slave Secondary Port"


Advarsel
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.