Sunwoda
Understøttede Enheder
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| OSP-100K-A | ✅ | ✅ | ❌ |
| OSP-200K-A | |||
| OSP-200K-A2 | |||
| OSP-300K-A3 | |||
| OSP-400K-A2 | |||
| OSP-400K-A4 | |||
| OSP-100K-B | |||
| OSP-200K-B | |||
| OSP-200K-B2 | |||
| OSP-100K-C-2 | |||
| OSP-100K-C-3 | |||
| OSP-200K-C | |||
| OSP-200K-C2 | |||
| OSP-100K-H-2 | |||
| OSP-100K-H-3 | |||
| OSP-200K-H | |||
| OSP-200K-H2 | |||
| Oasis 180 |
Forsigtighed
Forsigtighed
Vigtigt for batterier større end 100 kW
Hvis din batterikapacitet er vurderet til 100 kW eller mere, kontakt Sunwoda support for at udvide registeret for effektrestriktion.
Som standard er effektrestriktionen sat til 100 kW. Dette kan opdateres af Sunwoda support på register 0x78f6. SmartgridOne Controller vil derefter kunne styre effektrestriktionen.
Kabelføring
Ethernet
For korrekt ethernet kabelføring: Følg .
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485 A | RS485_POS | RS485 A | TX+ | |
| RS485 B | RS485_NEG | RS485 B | TX- | |
| RS GND | GND | Not available | G |
Konfiguration
Hvis du forbinder via TCP, skal du sikre dig, at enheden er konfigureret til at kommunikere på port 502.
Advarsel
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.