Carlo Gavazzi EM111 Contatore di Energia
Dispositivi Supportati
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Carlo Gavazzi EM111 | ❌ | ✅ |

Cablaggio
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Terminal 8 / A- | RS485 A | RS485_POS | RS485 A | TX+ |
| Terminal 6 / B+ | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
Configurazione
Verificare che il contatore Carlo Gavazzi sia impostato per leggere sia la potenza in importazione che in esportazione. Una modalità non adatta potrebbe causare:
- Mancata rilevazione dell'immissione in rete, oppure
- L’immissione in rete venga conteggiata come prelievo (oltre al ‘prelievo effettivo’)
Puoi impostarlo nel menu di configurazione ‘MEASurE’ sul contatore di energia. Dovrebbe essere impostato su ‘b’.
Avviso
Avviso
Questa impostazione potrebbe non essere presente sui modelli certificati MID (numeri di modello terminanti in PFA e PFB).

Avviso
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.