Contatori Energetici Pilota
Dispositivi Supportati
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Pilot SPM33 | ✅ | ✅ |
Cablaggio
RS485
I terminali RS485 si trovano sul retro del dispositivo.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| 13 (A+) | RS485 A | RS485_POS | RS485 A | TX+ |
| 12 (B-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 14 (Shield) | RS GND | GND | Not available | G |
Nota
Nota
Alimentazione Assicurarsi che il dispositivo sia alimentato utilizzando i terminali 1 (L/+) e 3 (N/-). L'intervallo di alimentazione ausiliaria è AC 85-265V o DC 100-300V.
Configurazione
Avviso
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Utilizzare le seguenti impostazioni Modbus nella procedura guidata dispositivo di Controller. Queste sono le impostazioni predefinite per il contatore:
- Baudrate: 9600
- Indirizzo Modbus: 1 (o l'indirizzo impostato sul contatore)
- Parità: Nessuna
- Bit di stop: 1
- Bit di dati: 8