Inepro Energiezähler
Unterstützte Geräte
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Inepro PRO380 | ❌ | ✅ |
Verkabelung
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A (pin 22) | RS485 A | RS485_POS | RS485 A | TX+ |
| B (pin 23) | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |

Konfiguration
Warnung
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Weitere Informationen zur Änderung der Modbus-Adresse finden Sie im Handbuch des Zählers. Standardmäßig ist der Zähler auf Adresse 1 eingestellt. Diese kann über das Zählerdisplay geändert werden.
- Benutzen Sie die Tasten, um in den Programmiermodus 2 zu gelangen.
- Drücken und halten Sie die rechte Taste für 3 Sekunden, um das Menü zu öffnen.
- Blättern Sie zur LCD-Seite Modbus/M-bus ID (addr xxx).
- Drücken und halten Sie die rechte Taste für 5 Sekunden, um den Programmiermodus zu betreten.
- Der Wert beginnt zu blinken: Wählen Sie 3 Ziffern (Modbus: 001-247). Bestätigen Sie jede Ziffer, indem Sie beide Tasten für 3 Sekunden gedrückt halten.
- Das LCD zeigt OK an, wenn die Einstellung bestätigt wurde.