Sigenergy Omvormers
Ondersteunde Apparaten
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|---|
| SigenStor | - | ✅ | ✅ | ✅ |
| PV Max | ||||
| Hybrid |
Bekabeling
De SmartgridOne Controller en de Dyness omvormers communiceren via RS485 of Ethernet.
Ethernet
Voor correcte ethernet bekabeling: Volg de richtlijnen voor ethernet bekabeling.
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
Configuratie
Zorg dat modbus is ingeschakeld:
- Ga vanaf de hoofd pagina naar "Device"
- Klik op "Powerhouse Settings"
- Schakel "Modbus TCP Server Enable" in

Zorg dat de omvormer is ingesteld op Remote EMS Mode:
- Ga vanaf de hoofdpagina naar "System"
- Klik op de drie puntjes naast de installatie namespace
- Klik op "System Settings"
- Klik op "Operational Mode"
- Selecteer "Remote EMS Mode"

Schakel eventuele netlimieten uit:
- Ga vanaf de hoofdpagina naar "System"
- Klik op de drie puntjes naast de installatie namespace
- Klik op "System Settings"
- Onder "Operational Parameters" schakel "Export Limitation" en "Import Limitation" uit
- Stel "Grid Connection Point Reserve Power Control Method" in op "Power Per Phase"

Waarschuwing
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.