SmartgridOne logo
SmartgridOne logo
AppCertifikaterController
Eksterne Signaler
Enheder
Elbilopladningsstation
Energimåler
ABBAccuenergyAcrelAlgodueBilagBMR
Carlo Gavazzi
ChargeeChintCloud-målerdataDornscheidt
Eastron
Eniris
FluviusFroniusHagerHomeWizardHuaweiIneproIskra
Janitza
JoulzKaifaKamstrupKlar til SmartgridLandis+GyrLegrandLitiotM-BusMetcomP1ApiPhoenix-ContactPilotSagemcom
Schneider
Self configured energy meterSeneca S604SessyShelly Energi målereSiemensSmappeeSocomecSolax
Solis
Solis EnergimeterSolis nettilsluttet energimåler
SunwodaTillquistVictronWeidmüllerYouLessZendure P1 MålerZiv
Gasmåler
Kedel
Nye integrationer
Plc
Pv Hybrid- og batteri-invertere
Sky
Vandmåler
Varmepumpe
Vekslende Belastninger
Fejlfinding
InstallationKom godt i gang
Konfiguration fra A til Z
Kontrolresponstid
Kundespecifik
LicensNetværkRetningslinjer for ledningsføring og tilslutningSikkerhed, vedligeholdelse og juridiske meddelelserSpecifikationerStatus-LED'er
Tilbehør
Værktøjskasse
Videovejledninger
EnhederEnergimålerSolis

Solis nettilsluttede energimålere

Solis

Understøttede enheder

Device TypeModbus TCP (Ethernet)RS485
Solis Grid-Tie Meter (via Inverter/EPM)✅✅
Autarco Grid-Tie Meter (via Inverter/EPM)

Forbindelse

Ethernet

For korrekt ethernet-installation: Følg vejledningen til ethernet-installation.

RS485

Tilslut RS485-ledningerne til kommunikationsporten på Solis-enheden (Inverter eller Export Power Manager).

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
ARS485 ARS485_POSRS485 ATX+
BRS485 BRS485_NEGRS485 BTX-
GND (optional)RS GNDGNDNot availableG

Konfiguration

Advarsel
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Sørg for, at enheden er konfigureret med følgende Modbus-indstillinger, så de matcher driverens specifikationer:

  • Baudrate: 9600
  • Databits: 8
  • Stopbits: 1
  • Parity: Ingen
  • Modbus-adresse: 1 (standard) - Interval: 1 til 254