Pilot Energi Målere
Understøttede enheder
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Pilot SPM33 | ✅ | ✅ |
Kabelføring
RS485
RS485-terminalerne er placeret på bagsiden af enheden.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| 13 (A+) | RS485 A | RS485_POS | RS485 A | TX+ |
| 12 (B-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 14 (Shield) | RS GND | GND | Not available | G |
Note
Note
Strømforsyning Sørg for, at enheden forsynes med strøm via terminalerne 1 (L/+) og 3 (N/-). Det hjælpeforsyningsområde er AC 85-265V eller DC 100-300V.
Konfiguration
Advarsel
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Brug følgende Modbus-indstillinger i Controller's device wizard. Dette er standardindstillingerne for måleren:
- Baudrate: 9600
- Modbus-adresse: 1 (eller den adresse, der er sat på måleren)
- Paritet: Ingen
- Stop bits: 1
- Data bits: 8