Carlo Gavazzi EM111 Energimåler
Understøttede enheder
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Carlo Gavazzi EM111 | ❌ | ✅ |

Kabelføring
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Terminal 8 / A- | RS485 A | RS485_POS | RS485 A | TX+ |
| Terminal 6 / B+ | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
Konfiguration
Kontroller, at Carlo Gavazzi måleren er sat til at aflæse både import og eksport effekt. En uhensigtsmæssig indstilling kan føre til:
- Manglende aflæsninger af tilførsel, eller
- At tilførsel tælles som forbrug (udover det ‘reelle forbrug’)
Du kan sætte dette i ‘MEASurE’ konfigurationsmenuen på elmåleren. Denne bør være sat til ‘b’.
Advarsel
Advarsel
Denne indstilling kan muligvis ikke findes på MID-certificerede modeller (modelnumre der ender på PFA og PFB).

Advarsel
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Sæt Modbus-adressen gennem elmålerens “Address” konfigurationsmenu.