Eniris Pulse‑based Water Meters

Eniris

Supported Devices

The integration is intended for any water meter that offers a clean pulse output (normally‑open or normally‑closed contact). Typical examples are the popular ZENNER, Itron, Kamstrup, or Sensus models equipped with pulse modules – but any dry‑contact 1 pulse = x l counter will work.

Device Type
Generic pulse water meter

Wiring

Pulses are read via the digital input (DIA/DIB) of the Controller or Smart Grid Controller. Wire the meter’s open‑collector or reed switch as illustrated below:

Pulse wiring
  • Polarity does not matter for dry contacts.* Use twisted pair cable for long distances (> 10 m) to minimise interference.

Configuration in the Eniris Portal

  1. Add a new device and select “Generic Digital Input → Water Meter”.
  2. Choose the digital input (DIA or DIB) you have connected the meter to.
  3. Enter the pulses per m³ (e.g. 1000 pulses/m³ for many domestic meters).
  4. Save — the driver will immediately start logging cumulative consumption and flow‑rate.

Tip : If you see negative deltas, invert the wiring or change the input logic from normally‑open to normally‑closed in the device settings.

Metrics exposed

KeyDescriptionUnit
flowRate_lpsInstantaneous flow rateL/s
importedAbsWaterTot_lTotal volume consumedL
importedWaterDeltaTot_lDelta volume since last periodL

All metrics are stored in the waterMeterMetrics measurement and retained with 1 s resolution by default.

Troubleshooting

  • No data? Check that the contact actually toggles using a multimeter or LED tester, and verify the correct digital input is selected.
  • Erratic pulses? Add a 1 kΩ pull‑up resistor or enable the built‑in pull‑up in the controller.
  • Flow too high/low? Confirm the pulses per m³ factor from the meter datasheet.

Need help? Reach out to SmartgridOne support at support@eniris.io.