Daikin

Daikin Altherma 3 Heatpumps

Supported Devices

Device TypeAPIModbus TCP (Ethernet)RS485Relays
EHV*
ETV*
warning

Control is only possible using Boost or Block. Specific Wattage control is not supported!

Connection

The communication between the SmartgridOne Controller and the Daikin heatpump operates via Relays. This guide follows the installation of the installer reference guide.

1. Preparation

Turn off the heat pump completely by disconnecting the power supply to the heat pump.

2. Opening the Switchbox

Follow the steps as described in section 7.2.4 - To open the indoor unit of the installers reference guide:

  • Remove the MMI plate.
  • Then remove the front plate.

3. Locating Terminal Block X5M

Locate terminal block X5M inside the unit. On this terminal block, you will find:

  • Positions 9-10: S10S (12V)
  • Positions 5-6: S11S (12V)

4. Wiring to the Controller

For the connection between the SmartgridOne Controller and the Daikin Altherma heat pump wire with 0.5mm2 cross section is required. Wire the heat pump to the controller as follows:

Terminal X5MController
9R1 NO
10R1 COM
5R2 NO
6R2 COM

5. Adding the Heat Pump to the Controller

In the controller interface, navigate to: Devices > Start device wizard > Heat Pump > Generic > Relays > Relay-controlled heat pump > My device is fully connected

Then enter the following data:

  • An estimate of the maximum required power for the heat pump at that location.

Continue through the wizard to complete the setup.

You may modify the device settings afterward as desired, but the default values are sufficient in most cases.

6. Reconnecting the Heat Pump

Once the wiring is complete, you may power the heat pump back on.

7. Configuration via MMI

Using the heat pump's MMI, enter installer mode and set the following parameters:

BreadcrumbValueName
9.8.43 = Smart GridBenefit kWh power supply
9.8.5set as desiredSmart Grid operation mode
9.8.6set as desiredAllow electrical heaters
9.8.7set as desiredEnable room buffering
9.8.8set as desiredLimit setting kW

💡 Tip: To turn on the breadcrumbs press the (i) button on the MMI while on the homescreen.


After completing these steps, the heat pump will be properly connected, registered in the software, and configured for use via relay control.