Stödda enheter
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric IEM 3150 | ❌ | ✅ |
| Schneider-Electric IEM 3155 | ||
| Schneider-Electric IEM 3250 | ||
| Schneider-Electric IEM 3255 | ||
| Schneider-Electric IEM 3350 | ||
| Schneider-Electric IEM 3355 | ||
| Schneider-Electric IEM 3455 | ||
| Schneider-Electric IEM 3555 |
Varning
Varning
Inte alla Schneider-Electric IEM 3000-seriens energimätare registrerar exporterad energi! Kontrollera med tillverkaren av energimätaren vid tveksamhet. Åtminstone tillåter inte IEM 3150, IEM 3250 och IEM 3350 att läsa ut exporterad energi.

Kabeldragning
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V | RS GND | GND | Not available | G |