Dysun Energy

Supported Devices

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
Hybrid inverterDysun Hybrid✅✅❌
FlexAmpFlexAmp One 3.6K, 5K, 8K, 10K, 12K❌✅

Wiring

Dysun Hybrid

Modbus TCP

  • Connect the inverter's LAN port to your local network.
  • Default port: 502.
  • The Modbus unit ID must be set between 1–247 (default 1).

RS485

معلومات
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
RS485-ARS485 ARS485_POSRS485 ATX+
RS485-BRS485 BRS485_NEGRS485 BTX-
GNDRS GNDGNDNot availableG

Serial settings:

ParameterValue
Baud rate9600 (default) or as configured in the inverter menu
Data bits8
ParityNone
Stop bits1

FlexAmp

The FlexAmp series communicates exclusively over RS485.

معلومات
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
RS485-ARS485 ARS485_POSRS485 ATX+
RS485-BRS485 BRS485_NEGRS485 BTX-
GNDRS GNDGNDNot availableG

Serial settings:

ParameterValue
Baud rate9600 (default)
Data bits8
ParityNone
Stop bits1

Configuration

تحذير
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
  • Set the Modbus address (slave ID) between 1–247 in the device menu.
  • Each device on the RS485 bus must have a unique address.

FlexAmp Setup

During device scanning or manual configuration, you will be prompted:

"What is included in the installation?"

OptionWhen to select
Solar panels and battery (default)Both PV and battery are installed
Only solar panelsNo battery is present
Only batteryNo PV is present

Select the option that matches your installation. An incorrect selection will result in missing or incorrect measurements.

Control

Dysun Hybrid

The inverter supports battery control:

  • Charge mode: Set charge current in amperes
  • Discharge mode: Set discharge power as a percentage of nominal power
  • When smart grid control is disabled, the inverter returns to autonomous operation
تنبيه
تنبيه

Experimental Control features for the Dysun Hybrid have not been validated on live hardware.


FlexAmp

The FlexAmp series supports PV curtailment — the controller can limit the maximum solar production power in real time.

  • The active power limit is written as a percentage of nominal power.
  • When smart grid control is disabled, the device reverts to its configured local settings (typically unrestricted output).
  • Curtailment applies to the total production of all connected PV strings.
ModelRated powerMax curtailment resolution
FlexAmp One 3.6K3 600 W1 W
FlexAmp One 5K5 000 W1 W
FlexAmp One 8k8 000 W1 W
FlexAmp One 10k10 000 W1 W
FlexAmp One 12k12 000 W1 W