Skip to main content
logo

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
Metcom MCS301

Wiring

Ethernet

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
A RS485 ARS485_POSRS485 ATX+
B RS485 BRS485_NEGRS485 BTX-
N/A RS GNDGNDNot availableG
Image 1

Configuration

Ethernet

View the manual for more information on configuration.

Image 1

RS485

View the manual for more information. The energy meter uses the DLMS/COSEM broadcast protocol, so it should not be necessary to set an address.