Teltonika EV Charging Stations

Supported Devices

Device TypeVariantsModbus TCP (Ethernet)RS485
TeltoCharge7.4kW/11kW/22kW

Connection

TeltoCharge Wiring

The communication between the SmartgridOne Controller and the TeltoCharge operates via an RS-485 serial bus or Modbus TCP.

It is recommended to use shielded cables with twisted pairs for optimal performance. For short distances, a twisted pair from a network cable (minimum CAT5e) can be used.

The following guidelines apply:

  • Maximum Distance: The total cable length, including the main cable and branches, is limited to 100 meters.
  • Connecting Multiple Inverters: The cable should be daisy-chained from meter to meter or branched off the main cable (branches must not exceed 1 meter).
  • Long Distances: It is recommended to install a 120Ω termination resistor at the end of the main cable and activate the termination resistor on the SmartgridOne Controller.

Example of cable setup:

Cable WireCharging StationSmartgridOne ControllerRS485 USB
Modbus CableTerminal RS485 ATerminal RS485 ATerminal RS485 A
Modbus CableTerminal RS485 BTerminal RS485 BTerminal RS485 B
ShieldTerminal RS485 GNDTerminal RS485 GNDTerminal RS485 GND

Settings

The TeltoCharge needs to have modbus enabled:

  1. Open the Teltonika app
  2. Navigate to "Settings" -> "Installer Menu"
  3. Enable "Dynamic Load Balancing"
  4. After doing this "Dynamic Load Management" will become visisble
  5. Scroll down and enable "Dynamic Load Management"
  6. Click "Save"
  7. The TeltoCharge will now reboot and modbus will be enabled
note

If you have multiple charging stations it is important to set the modbus addresses, each charging station should have a different address.