Inversores Dyness
Dispositivos Suportados
Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
---|---|---|---|---|
EC100 | 100kWh | ✅ | ✅ | ✅ |
DH100F | 71~100kWh | |||
DH200F | 100kW/215kWh | |||
DH200Y | 100kW/232kWh | ❌ |
Fiação
O SmartgridOne Controller e os inversores Dyness se comunicam via RS485 ou Ethernet.
Ethernet
Para uma fiação ethernet correta: Siga as diretrizes para fiação ethernet.
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
COM6 terminal 1A | RS485 A | RS485_POS | RS485 A | TX+ |
Com6 terminal 1B | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |

Configuração
DH100F
O Dyness DH100F precisa ser configurado para o modo remoto:
- Clique no ícone do menu principal no canto superior direito da interface principal
- Clique em "Dados" na barra de menu principal
- Clique em "EMS" na barra de submenu
- Clique em "RunSet" no canto superior esquerdo da barra de navegação
- Defina o Modo de Controle para "Remoto"

NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.