Pular para o conteúdo principal

DEYE

logo

Dispositivos Suportados

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
SG04LP3-EUSUN-5/6/8/10/12K
SG01LP1-EUSUN-12/14/16K

Fiação

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
Pin 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
Pin 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
Pin 3 / GND_485 RS GNDGNDNot availableG
Image 1
Image 1
Image 1

Configuração

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Vá para “Tela Principal” >> “Configurações do Sistema” >> “Função Avançada.”

  • O SN do Modbus deve ser configurado para qualquer número entre 1 e 247. Não selecione 0!! Observe que, se houver vários dispositivos no barramento RS485, cada um deve ter um número exclusivo. Este é o endereço.
  • O Slave deve ser marcado.
  • Somente quando um medidor adicional estiver conectado diretamente ao inversor, o “EX_meter Para CT” deve ser marcado. Se houver apenas um medidor em paralelo com o SmartgridOne Controller, ele deve ser desmarcado.
  • Certifique-se de que as seguintes configurações estão todas corretas: "Max A Charge", "Max A Discharge", "Grid Charge Ampere"
Image 1