Pular para o conteúdo principal
logo

Dispositivos Suportados

Device TypeModbus TCP (Ethernet)RS485
Schneider-Electric IEM 3150
Schneider-Electric IEM 3155
Schneider-Electric IEM 3250
Schneider-Electric IEM 3255
Schneider-Electric IEM 3350
Schneider-Electric IEM 3355
Schneider-Electric IEM 3455
Schneider-Electric IEM 3555
atenção

Nem todos os medidores de energia da série IEM 3000 da Schneider-Electric registram energia exportada! Verifique com o fabricante do medidor de energia em caso de dúvida. Pelo menos IEM 3150, IEM 3250 e IEM 3350 não permitem a leitura da energia exportada.

Imagem 1

Fiação

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
D1 RS485 ARS485_POSRS485 ATX+
D0 RS485 BRS485_NEGRS485 BTX-
0V RS GNDGNDNot availableG
Imagem 1

Configuração

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Verifique o manual do dispositivo sobre como acessar o menu de configuração do medidor de energia.

Imagem 1
Imagem 1