Dispositivos Suportados
Device Type | Modbus TCP (Ethernet) | RS485 |
---|---|---|
Inepro PRO380 | ❌ | ✅ |
Fiação
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
A (pino 22) | RS485 A | RS485_POS | RS485 A | TX+ |
B (pino 23) | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |

Configuração
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Consulte o manual do medidor para informações mais detalhadas sobre a alteração do endereço Modbus. Por padrão, o medidor está configurado para o endereço 1. Isso pode ser alterado através do display do medidor.
- Use os botões para ir para o Modo de Programação 2.
- Pressione e segure o botão direito por 3 segundos para abrir o menu.
- Role até a página LCD ID Modbus/M-bus (endereço xxx).
- Pressione e segure o botão direito por 5 segundos para entrar no modo de programação.
- O valor começa a piscar: selecione 3 dígitos (Modbus: 001-247). Confirme cada dígito segurando os dois botões por 3 segundos.
- O LCD mostra OK quando a configuração é confirmada.