Bedrading

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
Pin 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
Pin 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
Pin 3 / GND_485 RS GNDGNDNot availableG
Afbeelding 1
Afbeelding 1
Afbeelding 1

Configuratie

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Ga naar “Hoofdscherm” >> “Systeeminstellingen” >> “Geavanceerde functie.”

  • Modbus SN moet worden ingesteld op elk nummer tussen 1 en 247. Selecteer geen 0!! Merk op dat als er meerdere apparaten op de RS485-bus zijn, elk een uniek nummer moet krijgen. Dit is het adres.
  • Slave moet worden aangevinkt.
  • Alleen wanneer een extra meter direct op de omvormer is aangesloten, moet “EX_meter For CT” worden aangevinkt. Als er slechts één meter parallel staat met de SmartgridOne Controller, moet deze niet aangevinkt zijn.
  • Zorg ervoor dat de volgende instellingen allemaal correct zijn: "Max A Opladen", "Max A Ontladen", "Netbelasting Ampère"