Aller au contenu principal
logo

Inverseurs Dyness

Appareils Supportés

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
EC100100kWh
DH100F71~100kWh
DH200F100kW/215kWh
DH200Y100kW/232kWh

Câblage

Le SmartgridOne Controller et les inverseurs Dyness communiquent via RS485 ou Ethernet.

Ethernet

Pour un câblage ethernet correct : Suivez les directives pour le câblage ethernet.

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
COM6 terminal 1A RS485 ARS485_POSRS485 ATX+
Com6 terminal 1B RS485 BRS485_NEGRS485 BTX-
N/A RS GNDGNDNot availableG
Câblage Dyness

Configuration

DH100F

Le Dyness DH100F doit être réglé en mode distant :

  1. Cliquez sur l'icône du menu principal en haut à droite de l'interface principale
  2. Cliquez sur "Données" dans la barre de menu principal
  3. Cliquez sur "EMS" dans la barre de sous-menu
  4. Cliquez sur "RunSet" en haut à gauche de la barre de navigation
  5. Réglez le Mode de Contrôle sur "Distant"
Interface Dyness DH100F
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.