Onduleurs Ampowr
Appareils pris en charge
Device Type | Variants | Modbus TCP (Ethernet) | RS485 |
---|---|---|---|
Ampihome | Monophasé | ❌ | ✅ |
Triphasé | ❌ |
Câblage
Le SmartgridOne Controller et les onduleurs Ampihone communiquent via RS485 ou Ethernet.
Ethernet
Pour un câblage Ethernet correct : Suivez les directives pour le câblage Ethernet.
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
Pin 7 (Blanc-Marron) | RS485 A | RS485_POS | RS485 A | TX+ |
Pin 8 (Marron) | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |

Configuration
Ampihome Monophasé
L'Ampihome Monophasé doit être configuré sur le Port Secondaire Esclave :
- Ouvrez l'application ESS Link
- Sélectionnez "Mon" dans le coin inférieur droit
- Sélectionnez "Mon Appareil"
- Sélectionnez le "N° Comm." de l'appareil
- Sélectionnez "Paramètres des Paramètres"
- Réglez "Mode de Fonctionnement" sur "Mode de Charge Programmée (C&D)"
- Sélectionnez "Avancé" dans le coin supérieur droit
- Réglez "Multiplexage BMS1 RS485" sur "Port Secondaire Esclave"


NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.