Appareils pris en charge
Device Type | Modbus TCP (Ethernet) | RS485 |
---|---|---|
Inepro PRO380 | ❌ | ✅ |
Câblage
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
A (broche 22) | RS485 A | RS485_POS | RS485 A | TX+ |
B (broche 23) | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |

Configuration
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Consultez le manuel du compteur pour des informations plus détaillées sur le changement de l'adresse Modbus. Par défaut, le compteur est réglé sur l'adresse 1. Cela peut être changé via l'affichage du compteur.
- Utilisez les boutons pour accéder au Mode Programme 2.
- Appuyez et maintenez le bouton de droite pendant 3 secondes pour ouvrir le menu.
- Faites défiler jusqu'à la page LCD Modbus/M-bus ID (addr xxx).
- Appuyez et maintenez le bouton de droite pendant 5 secondes pour entrer en mode programmation.
- La valeur commence à clignoter : sélectionnez 3 chiffres (Modbus : 001-247). Confirmez chaque chiffre en maintenant les deux boutons enfoncés pendant 3 secondes.
- L'affichage LCD affiche OK lorsque le paramètre est confirmé.