Accuenergy

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
Acuvim IIR Energy Meter
Acuvim 3 Energy Meter

Connection

Ethernet

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

If you have an accuenergy energy meter you should have an interface to manage it, in this interface go to the Settings page, then select the Communications menu.

Header of the Settings>Communication

Then scroll until you find these fields :

Modbus settings
attention

Be sure that the port is set to 502 and the Fast Read Mode is enabled and set to 100ms Fast Read.

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
RS485 ARS485_POSRS485 ATX+
RS485 BRS485_NEGRS485 BTX-
RS GNDGNDNot availableG
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.