Zum Hauptinhalt springen

DEYE

logo

Unterstützte Geräte

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
SG04LP3-EUSUN-5/6/8/10/12K
SG01LP1-EUSUN-12/14/16K

Verkabelung

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
Pin 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
Pin 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
Pin 3 / GND_485 RS GNDGNDNot availableG
Bild 1
Bild 1
Bild 1

Konfiguration

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Gehe zu „Hauptbildschirm“ >> „Systemeinstellungen“ >> „Erweiterte Funktion.“

  • Modbus SN sollte auf eine Zahl zwischen 1 und 247 eingestellt sein. Wähle nicht 0!! Beachte, dass, wenn mehrere Geräte am RS485-Bus sind, jedes eine eindeutige Nummer erhalten sollte. Dies ist die Adresse.
  • Slave sollte aktiviert sein.
  • Nur wenn ein zusätzlicher Zähler direkt mit dem Wechselrichter verbunden ist, sollte „EX_meter Für CT“ aktiviert sein. Wenn es nur einen Zähler parallel zu SmartgridOne Controller gibt, sollte dies deaktiviert sein.
  • Stelle sicher, dass die folgenden Einstellungen alle korrekt sind: "Max A Charge", "Max A Discharge", "Grid Charge Ampere"
Bild 1