Tesvolt

Tesvolt

Supported Devices

Device TypeModbus TCP (Ethernet)RS485Curtailment
Energy Manager

Wiring

The communication between the SmartgridOne Controller and the Tesvolt system operates via Modbus TCP. For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

Energy Manager

Tesvolt Energy Manager Configuration

Steps
1a. Open the Tesvolt Energy Manager web interface. Request the link to the portal, and its login credentials from your installer
1b. Go to Remote Control Signals under Device Settings and press Configure a Remote Control Signal: Image
1c. Configure the device with the correct IP address(Listen Address) and slave address(Unit ID) and press Save: Image

Troubleshooting

Inside the Tesvolt Energy manager web interface, it's possible to check the signals that are sent by the SmartgridOne Controller to the Tesvolt Energy Manager. It can be reached using this way:

Groups example

PV control issues:

If any issues occur related to PV control, check if the following value corresponds with the value set by the controller:

Groups example

Battery control issues:

If any issues occur related to battery control, check if the following value corresponds with the value set by the controller:

Groups example