Dyness 逆变器
支持的设备
Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
---|---|---|---|---|
EC100 | 100kWh | ✅ | ✅ | ✅ |
DH100F | 71~100kWh | |||
DH200F | 100kW/215kWh | |||
DH200Y | 100kW/232kWh | ❌ |
接线
SmartgridOne Controller 和 Dyness 逆变器通过 RS485 或以太网进行通信。
以太网
正确的以太网接线:请遵循 以太网接线指南。
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
COM6 terminal 1A | RS485 A | RS485_POS | RS485 A | TX+ |
Com6 terminal 1B | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |

配置
DH100F
Dyness DH100F 需要设置为远程模式:
- 点击主界面右上角的主菜单图标
- 在主菜单栏中点击“数据”
- 在子菜单栏中点击“EMS”
- 在导航栏左上角点击“RunSet”
- 将控制模式设置为“远程”

NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.