DEYE

شعار

الأجهزة المدعومة

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
SG04LP3-EUSUN-5/6/8/10/12K
SG01LP1-EUSUN-12/14/16K

الأسلاك

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
دبوس 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
دبوس 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
دبوس 3 / GND_485 RS GNDGNDNot availableG
صورة 1
صورة 1
صورة 1

الإعداد

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

اذهب إلى “الشاشة الرئيسية” >> “إعدادات النظام” >> “وظيفة متقدمة.”

  • يجب أن يكون Modbus SN مضبوطًا على أي رقم بين 1 و 247. لا تحدد 0!! لاحظ أنه إذا كان هناك أجهزة متعددة على ناقل RS485، يجب إعطاء كل جهاز رقمًا فريدًا. هذه هي العنوان.
  • يجب أن تكون خانة "Slave" محددة.
  • فقط عندما يتم توصيل عداد إضافي مباشرة بالع inverter يجب تحديد خانة “EX_meter For CT”. إذا كان هناك فقط عداد متصل بشكل متوازي مع SmartgridOne Controller يجب إلغاء تحديدها.
  • تأكد من أن الإعدادات التالية صحيحة تمامًا: "حد أقصى للتيار عند الشحن"، "حد أقصى للتيار عند التفريغ"، "تيار شبكة الشحن"
صورة 1