انتقل إلى المحتوى الرئيسي
شعار

الأجهزة المدعومة

Device TypeModbus TCP (Ethernet)RS485
Inepro PRO380

التوصيل

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
A (دبوس 22) RS485 ARS485_POSRS485 ATX+
B (دبوس 23) RS485 BRS485_NEGRS485 BTX-
N/A RS GNDGNDNot availableG
صورة 1

الإعداد

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

يرجى الرجوع إلى دليل العداد لمزيد من المعلومات التفصيلية حول تغيير عنوان Modbus. بشكل افتراضي، يتم تعيين العداد على العنوان 1. يمكن تغيير هذا من خلال شاشة العداد.

  1. استخدم الأزرار للانتقال إلى وضع البرنامج 2.
  2. اضغط مع الاستمرار على الزر الأيمن لمدة 3 ثوان لفتح القائمة.
  3. قم بالتمرير إلى صفحة LCD ID Modbus/M-bus (addr xxx).
  4. اضغط مع الاستمرار على الزر الأيمن لمدة 5 ثوانٍ للدخول إلى وضع البرمجة.
  5. يبدأ القيمة في الومض: اختر 3 أرقام (Modbus: 001-247). أكد كل رقم بالضغط معًا على كلا الزرين لمدة 3 ثوانٍ.
  6. تظهر على شاشة LCD OK عند تأكيد الإعداد.
صورة 1